MO16 8″ RO System

Ecosoft MO16 industrial reverse osmosis system is a turnkey solution for industrial water challenges, that includes pilot studies, engineering and manufacturing, commissioning and maintenance. Ecosoft reverse osmosis systems are used in food and pharmaceutical industry, energy, chemical, semiconductor manufacturing, steam boilers and other industrial applications.

FEATURES

  • Energy efficiency with Grundfos pump
  • Reliable performance with quality components and engineering
  • Individual project evaluation per request
  • ISO 9001 certified factory
  • CE marked and confirmed to be safe in accordance with EC New Approach Directives

HOW IT WORKS

TECHNICAL INFORMATION

Equipment

  • Grundfos® CR 32-6 high pressure pump – 1 pcs
  • 8040-4 membrane vessel – 4 pcs
  • Stainless steel housing with 7 PP 2,5 × 40″ filters – 1 pcs
  • Motorized butterfly valves (feed water in, flush out) – 2 pcs
  • Balancing valves (concentrate reject, concentrate recycle) – 2 pcs
  • Electrical cabinet with Ecosoft controller – 1 set
  • Piping, instrumentation – 1 set
  • Steel frame – 1 set

Options

  • Filmtec™ XLE-440 / ECO PRO-440 or Ecosoft ELP-8040 membranes
  • Dosing pump for antiscalant or other RO chemicals
  • Permeate inlet for permeate membrane rinse
  • Raw water blending line

Сonnections

  • Influent water — DN80 (flange)
  • Permeate — DN65 (flange)
  • Concentrate — DN80 (flange)
  • CIP inlet — DN65 (flange)
  • CIP return — DN65 (flange)
  • CIP permeate — DN40 (G 1½″)

Technical data

  • Permeate capacity¹ — 16 m³/h
  • Permeate recovery² — 75%
  • Maximum TDS — 4500 mg/L
  • Influent flow demand — 20…25 m³/h (service)
  • Operating pressure — 8…12 bar
  • Maximum pressure — 14 bar
  • Electrical requirements — 380…400 V, 50 Hz (3 ph)
  • Electrical power — 11 kW
  • Prefilter rating — 5 μm
    ¹ depends on feed water TDS, temperature, and permeate recovery
    ² for low scaling/fouling water

Feed water requirements

  • TDS — 4500 mg/L
  • hardness — 150 mg/L CaCO₃
  • iron — 0.1 mg/L
  • manganese — 0.05 mg/L
  • hydrogen sulfide — none
  • silicate — 20 mg/L
  • residual chlorine — 0.1 mg/L
  • SDI — 5
  • chemical oxygen demand – 4 mg/L O₂

 

Download Technical Data Sheet